공기청정기와 공기청정장치에 의한 미생물과 바이러스의 제거 효과
(주)코리아스칼라
- 최초 등록일
- 2016.04.01
- 최종 저작일
- 2004.06
- 11페이지/
어도비 PDF
- 가격 4,200원
![할인쿠폰받기](/images/v4/document/ico_det_coupon.gif)
* 본 문서는 배포용으로 복사 및 편집이 불가합니다.
서지정보
ㆍ발행기관 : 한국실내환경학회
ㆍ수록지정보 : 한국실내환경학회지 / 1권 / 1호
ㆍ저자명 : 김호중, 이광희, 남기석, 성백린, 변종길, 최호선
영어 초록
The performance of various air-cleaning devices and an assembled air cleaner has been evaluated for the removal of biological pollutants in indoor air. Bacteria, fungi, and viruses were sprayed in a test chamber, and air samples in the chamber were taken for analysis. Air-cleaning devices - UV lamp, ion generator, an UV LED and plasma electricity dust collector - were tested for their ability in the removal of microorganisms in the air. The UV lamp and the ion generator tested exhbited complete sterilization effect within 4hrs of operation. Other devices were less effective: The extent of removal by the UV LED and the plasma electricity dust collector after 6hrs of operation was about 20% to 82%, depending on the microorganisms tested. The performance of an assembled air cleaner was much superior to individual air-cleaning devices: the extent of removal being 97.6%, 99.1%, 98.7%, and 93.7% for Staphylococcus aureus (Gram(+) bacteria), Escherichia coli (Gram(-) bacteria), Aspergillus niger and Penicillium funiculosum (fungi), respectively, after 3hrs of operation. The removal of influenza virus was even more effective, with 99.9% of removal within 25min of operation. The results show that the air cleaner is effective for the removal of microbial and viral pathogens in the air.